ID-FLX Lite & Telecom Global Guide
135
Setpoint group ATTsettings Related FW 2.5.0
Range [units] 0.0 .. 100.0 [%]
Default value 0 YES
Step 0.1
Comm object 11858 Related applications
Description
This setpoint is giving Load limit integration factor.
Load Integral
6 back to List of setpoints
Setpoint group Load limit Related FW 2.5.0
Range [units]
RPM, ECU:Load, CU:AI1, CU:AI2, CU:AI3, CU:AI4, CU:AI5, CU:AI6, CU:AI7,
CU:AI8, CU:AI9, AIO:IA1, AIO:AI2, AIO:AI3, AIO:AI4 [-]
Default value RPM YES
Step -
Comm object 11859 Related applications
Description
This setpoint is for Load limit comparetor with hysteresis analog input selection. Source can be adjusted
from controller RPM pick-up, ECU, analog inputs or from extension module inputs.
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Load CMP Input
6 back to List of setpoints
Setpoint group ATTsettings Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 95 YES
Step 1
Comm object 11860 Related applications
Description
Limit to close LOADSWITCH (PAGE 217).
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Load CMP Off
6 back to List of setpoints