ID-FLX Lite & Telecom Global Guide
136
Setpoint group Load limit Related FW 2.5.0
Range [units] -10000 .. +10000 [-]
Default value 90 YES
Step 1
Comm object 11861 Related applications
Description
Limit to open LOADSWITCH (PAGE 217).
Value of this Setpoint should be given in value of quantity without decimal point.
Example: When AIN is configured in such way that Load limit set on 5V to maintain the value
8.54bar, then the value inserted to this Setpoint is 854.
Load CMP On
6 back to List of setpoints
Group: Engine protection
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 300 [s]
Default value 5 -
Step 1
Comm object 8262 Related applications
Description
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure). The
protections are unblocked after the Protection del time. The time starts after reaching Start RPM.
Eng prot del
6 back to List of setpoints
Setpoint group Engine protection Related FW 2.5.0
Range [units] 0 .. 300 [s]
Default value 1 -
Step 1
Comm object 10131 Related applications
Description
Specific protection delay is possible to use on Binary Input 6. Delay is active for Wrn or Sd protection only –
not for functions like Rem Start/Stop. Protection delay is active for both Binary input NO / NC configuration.
BIN6 del starts after Eng prot del (page 136) when BI6 protection is configured “Running only”.
BIN6 delay