ID-FLX Lite & Telecom Global Guide
167
Setpoint group Date/Time Related FW 2.5.0
Range [units] No Func, AutoRun, AutoRegCMP, AutoBatt, AutoStop [-]
Default value No Func -
Step -
Comm object 11661 Related applications
Description
No Func
Operates just corresponding TIMER2 (PAGE 216) according the TIMER2 (PAGE 216)
setting, see Timer2repeat (page 168), Timer2 ON time (page 168),
Timer2Duration (page 168). Function operates in all OFF-MAN-AUT modes.
Default state.
AutoRun
Engine automatically starts and stops in AUT mode (similar to REM START/STOP
(PAGE 186), the same record in the history) according the TIMER2 (PAGE 216)
setting.
AutoRegCMP
Start and stop engine in AUT mode according to the SPEEDSWITCH (PAGE 217) - see
Reg CMP Input (page 130). The comparator function (output) works opposite
when Reg CMP On (page 130) < Reg CMP Off (page 131). The Timer2repeat
(page 168), Timer2 ON time (page 168), Timer2Duration (page 168) are not
important in this case.
AutoBatt
Engine starts when actual Battery voltage < Batt undervolt (page 142) + Batt volt
del (page 142) and stays running for Timer2Duration (page 168). Function
operates in AUT mode.
AutoStop
Engine is switched from AUT to MAN and stopped or stopped from MAN mode (like
by STOP button) when engine runs longer then Timer2Duration (page 168) on
actual RPM less or equal Idle speed (page 115) + 5% (fix limit). Function is not
active during engine start.
Timer2Function
6 back to List of setpoints