ID-FLX Lite & Telecom Global Guide
179
Setpoint group Act. Calls/SMS Related FW 2.5.0
Range [units] OFF, ON [-]
Default value -
Step -
Comm object 8484 Related applications
Description
Set this setpoint to YES if you want to get messages when a red (shutdown) alarm occurs.
Note: The target address (cellular network phone number or e-mail address) must be set correctly to the
setpoint(s) TelNo/Addr Ch1 resp. TelNo/Addr Ch1, 2 (page 179).
Red Alarm Msg
6 back to List of setpoints
Setpoint group Act. Calls/SMS Related FW 2.5.0
Range [units] [-]
Default value -
Step -
Comm object 9597 Related applications
Description
Enter either a valid cellular network phone number or e-mail address to this setpoint, where the alarm
messages shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“it
is supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it is
supposed to be the telephone number and active SMS is sent.
Note: These setpoints can be modified from PC only!
For cellular network numbers use either national format (i.e. like number you will dial if you want to make
a local call) or full international format with "+" character followed by international prefix at the beginning.
TelNo/Addr Ch1, 2
6 back to List of setpoints