EasyManuals Logo
Home>ComAp>Controller>InteliDrive Lite

ComAp InteliDrive Lite Global Guide

ComAp InteliDrive Lite
225 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #192 background imageLoading...
Page #192 background image
ID-FLX Lite & Telecom Global Guide
192
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 316
Description
Active input disables the Regulator PI loop and switches analog output to constant Reg Bias (page 127).
R Reg Disable
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 220
Description
DayCons is the counter which cumulates the instantanous consumption coming from ECU . It shows the
total consumption since the counter reset. Counte reset happen at the midnight of the controller clocks. LBI
Clear DayCons resets the counter DayCons.
Note: The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint FuelTankVolume (page 125).
Clear DayCons
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 221
Description
TripCon is the counter which cumulates the instantanous consumption coming from ECU. It shows the total
consuption since last reset by LBI Clear TripCon. This LBI resets the counter TripCons.
Note: The function works when the controller is connected to an ECU or in other case is consumption
counted from the changes of analog input value Fuel rate and setpoint FuelTankVolume (page 125).
Clear TripCons
6 back to List of LBI
Related FW 2.5.0 Related applications
Comm object 398
Description
FlowSwitch is protection to stop the engine in case the water not flow. Function is active in MAN and AUT
mode. Engine is switched to Cooling state when FlowSwitch is not closed within Flow SwitchDel (page
138) after running (Ready to load) engine state activation. Function stops the engine in AUT mode with
FlowSwitch indication in Alarm list and stays in AUT mode after Fault reset.
Alarm list and History indication = "Cd Flow Switch" (CoolDown is third engine protection type in ID-Lite).
Machine state stays in Cooling even the LBI FLow Switch is activated again during Cooling period.
Flow Switch
6 back to List of LBI

Table of Contents

Other manuals for ComAp InteliDrive Lite

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliDrive Lite and is the answer not in the manual?

ComAp InteliDrive Lite Specifications

General IconGeneral
BrandComAp
ModelInteliDrive Lite
CategoryController
LanguageEnglish

Related product manuals