Curve Min [Ω] Max [Ω] Units
VDO 10 Bar 10 180 Bar
VDO40-120°C 22 3200 °C
VDOLevel% 0 180 %
General line 1 0 1000 Ω
General line 2 0 1000 Ω
General line 3 0 1000 Ω
General line 4 0 1000 Ω
General line 5 0 1000 Ω
General line 6 0 1000 Ω
General line 7 0 1000 Ω
General line 8 0 1000 Ω
General line 9 0 1000 Ω
General line 10 0 1000 Ω
General line 11 0 1000 Ω
General line 12 0 1000 Ω
General line 13 0 1000 Ω
Note: Curves can be modified via InteliConfig. Some standard curves are also prepared in InteliConfig.
IMPORTANT: For right behavior of function Total Fuel Consumption, curve for analog input FUEL
LEVEL (PAGE 508) has to be in percentage.