InteliLite4 AMF20 Global Guide
228
Starting Oil Pressure
Setpoint group Engine settings Related FW 1.3.0
Range [units] Disabled / 0,1 .. 10,0 [bar]
Default value 4,5 bar Alternative config NO
Step 0,1 bar
Comm object 9681 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Oil pressure limit for starting. The controller will stop cranking (STARTER (PAGE 501) goes OFF) if the oil
pressure rises above this limit.
Option Disabled – when this option is selected, Oil Pressure value (value from CU analog Oil Pressure,
value from ECU analog Oil pressure and state of binary input Oil Pressure) is not used for disengagement
of starter and for engine running evaluation.
IMPORTANT: Value from analog input has higher priority than value from ECU.
6 back to List of setpoints
Glow Plugs Time
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0.0 .. Prestart Time (page 227) [s]
Default value 0.1 s Alternative config NO
Step 1.0 s
Comm object 14412 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
This setpoint defines the time before starting when logical binary output GLOW PLUGS (PAGE 484) will be
active.
6 back to List of setpoints