InteliLite4 AMF20 Global Guide
501
Related FW 1.3.0 Related applications AMF,MRS
Comm object 24
Description
This output is dedicated for starter motor control. The number of cranking attempts is adjusted by setpoint
Cranking Attempts (page 225) in Engine Settings group. Cranking fail pause is adjusted by setpoint
Cranking Fail Pause (page 226).
Image 8.57 Starter
The starter output opens when:
Starting RPM are reached
the "firing" speed is reached (gas engines only)
maximum time of cranking is exceeded
request to stop comes up
D+ value is higher than D+ Threshold (page 243)
Oil pressure value is higher than Starting Oil Pressure (page 228)
Generator voltage >25 % of Nominal Voltage Ph-N (page 211) or Nominal Voltage Ph-Ph
(page 211) (any phase)
Starter
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 26
Description
Logical binary output which is still in logical 0.
Still Log 0
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 27
Description
Logical binary output which is still in logical 1.
Still Log 1
6 back to Logical binary outputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals