InteliLite4 AMF20 Global Guide
225
Group: Engine settings
Subgroup: Starting
Fuel Solenoid
Setpoint group Engine settings Related FW 1.3.0
Range [units] Diesel / Gas [-]
Default value Diesel Alternative config NO
Step [-]
Comm object 9100 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Determines behavior of the Binary output FUEL SOLENOID (PAGE 477)
Diesel: Output is activated before binary output STARTER (PAGE 501). Lead of output is
adjusted via setpoint Fuel Solenoid Lead (page 235). The output is deactivated if
Emergency Stop comes or Gen-set is stopped and in pause between repeated starts.
Gas: Output is activated together with binary output IGNITION (PAGE 487) if RPM is over the
30 RPM (fixed value). Output is deactivated after stop command or in pause between
repeated start.
6 back to List of setpoints
Cranking Attempts
Setpoint group Engine settings Related FW 1.3.0
Range [units] 1 .. 10 [-]
Default value 3 Alternative config NO
Step 1
Comm object 8255 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Maximal number of cranking attempts.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals