InteliLite4 AMF20 Global Guide
246
Sd overspeed option will result in controller shutting down the engine and displaying Sd Starting
Overspeed alarm and NextStartAt option will result in controller stopping the engine and trying to start
again. The number of attempts is defined by Cranking Attempts (page 225).
6 back to List of setpoints
Underspeed Sd
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 .. Overspeed Sd (page 244) [%]
Default value 25% Alternative config NO
Step 1 % of Nominal RPM (page 216)
Comm object 8260 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for underspeed protection. Relative to the nominal speed.
6 back to List of setpoints
Oil Pressure Delay
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 3600.0 [s]
Default value 3.0 s Alternative config NO
Step 0.1 s
Comm object 65535 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Wrn Oil Pressure (page 551)/Sd Oil Pressure (page 565) user protection.
6 back to List of setpoints
Oil Pressure Wrn
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 10.0 [bar]
Default value 2.0 bar Alternative config NO
Step 0.1 bar
Comm object 65534 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for Wrn Oil Pressure (page 551) user protection.
6 back to List of setpoints