InteliLite4 AMF20 Global Guide
216
Nominal RPM
Setpoint group Basic settings Related FW 1.3.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 8253 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: To lock this setpoint against editing you also have to lock setpoint Nominal RPM 1 (page 372),
Nominal RPM 2 (page 377) and Nominal RPM 3 (page 382).
6 back to List of setpoints
Subgroup: Controller settings
Controller Mode
Setpoint group Basic settings Related FW 1.3.0
Range [units] OFF / MAN / AUTO / TEST [-]
Default value OFF Alternative config NO
Step [-]
Comm object 8315 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint can be used for changing the Controller mode remotely, e.g. via Modbus. Use the mode
selector on the main screen for changing the mode from the front panel. Use mode selector in the control
window for changing the mode from InteliConfig.
6 back to List of setpoints