InteliLite4 AMF20 Global Guide
217
Power On Mode
Setpoint group Basic settings Related FW 1.3.0
Range [units] Previous / OFF [-]
Default value Previous Alternative config NO
Step [-]
Comm object 13000 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint adjusts controller mode after power on of controller.
Previous When controller is power on, controller is switched to last mode before power off.
OFF When controller is power on, controller is switched to OFF Mode.
Note: Remote modes – In case that some LBI remote mode is activated during power on of controller
than this LBI has higher priority than this setpoint – controller mode is forced into mode selected via
LBI. After deactivation of LBI, controller is switched into value selected via setpoint Power On Mode
6 back to List of setpoints
Default Application Select
Setpoint group Basic settings Related FW 1.3.0
Range [units] AMF / MRS [-]
Default value AMF Alternative config NO
Step [-]
Comm object 12157 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
This setpoint defines the controller application.
AMF Normal AMF operation
MRS When MRS mode is selected the controller will not perform AMF functions anymore.
MCB button will be inactive and also mains measurement and protections will be
disabled. The controller will keep TEST mode and the Gen-set in AUTO mode will be
able to start by REMOTE START/STOP (PAGE 459) binary input.
6 back to List of setpoints
GCB Control Mode
Setpoint group Process Control Related FW 1.3.0
Range [units] Internal / Follow / External [-]
Default value Internal Alternative config YES