InteliLite4 AMF20 Global Guide
64
Image 5.5 Second screen of InteliConfig – select Serial link
Connection using WinScope1000
Image 5.6 WinScope1000 screen – select serial link
Note: Username and password are not mandatory.
5.2.3 Ethernet
It is possible to connect to the controller using Ethernet port either directly or using ComAp's AirGate service.
Direct connection
If you use a direct connection the controller needs to be reachable directly from the PC you use (i.e. one LAN
or WAN without any firewalls and other points that may not allow the connection). The following settings
should to be checked in the controller:
Controller Address (page 224) must be set to the same value as in the PC tool
IP Address Mode (page 354) can be set to AUTOMATIC when there is DHCP service available.
Otherwise it should be set to FIXED
IP Address (page 355) is either set automatically or it can be adjusted to a specific requested value
Subnet Mask (page 355) is either set automatically or it can be adjusted to a specific requested value
Gateway IP (page 356) can be set here when it is used