InteliLite4 AMF20 Global Guide
354
Group: CM-Ethernet
Subgroup:TCP/IP Settings
IP Address Mode
Setpoint group CM-Ethernet Related FW 1.3.0
Range [units] MANUAL / AUTOMATIC / DISABLED [-]
Default value AUTOMATIC Alternative config NO
Step [-]
Comm object 23939 Related applications AMF,MRS
Config level Standard
Setpoint visibility Only if relevant module is installed
Description
The setpoint is used to select the method how the ethernet connection is adjusted.
MANUAL The Ethernet connection is fixed by means of the setpoints IP Addr, NetMask,
GateIP, DNS IP Address.
This method should be used for a classic Ethernet or internet connection. When
this type of connection opens, the controller is specified by its IP address. This
means that it would be inconvenient if the IP address were not fixed (static).
AUTOMATIC The Ethernet connection setting is obtained automatically from the DHCP
server. The obtained settings are then copied to the related setpoints. If the
process of obtaining the settings from the DHCP server is not successful, the
value 000.000.000.000 is copied to the setpoint IP address and the module
continues to try to obtain the settings.
DISABLED The Ethernet terminal is disabled.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals