InteliLite4 AMF20 Global Guide
484
Related FW 1.3.0 Related applications AMF,MRS
Comm object 77
Description
This output is active when the generator voltage, frequency and voltage unbalance is within limits. It is
deactivated:
immediately when the voltage/frequency/voltage unbalance gets out of limits (when GCB is not
closed)
or
with an appropriate delay after the voltage/frequency/voltage unbalance has got out of limits (when
GCB is closed)
Generator Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will be active for exact time pre-set by setpoint
Glow Plugs Time (page 228) before every starting attempt. The output is deactivated at the same time
as the STARTER (PAGE 501) output is activated (100ms after PRESTART (PAGE 496) output is deactivated).
Image 8.41 Glow Plugs
Glow Plugs