InteliLite4 AMF20 Global Guide
484
Related FW 1.3.0 Related applications AMF,MRS
Comm object 77
Description
This output is active when the generator voltage, frequency and voltage unbalance is within limits. It is
deactivated:
immediately when the voltage/frequency/voltage unbalance gets out of limits (when GCB is not
closed)
or
with an appropriate delay after the voltage/frequency/voltage unbalance has got out of limits (when
GCB is closed)
Generator Healthy
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1252
Description
This output is dedicated for diesel engine only. This output will be active for exact time pre-set by setpoint
Glow Plugs Time (page 228) before every starting attempt. The output is deactivated at the same time
as the STARTER (PAGE 501) output is activated (100ms after PRESTART (PAGE 496) output is deactivated).
Image 8.41 Glow Plugs
Glow Plugs