InteliLite4 AMF20 Global Guide
496
LBO: P
Related FW 1.3.0 Related applications AMF,MRS
Comm object 115
Description
The LBO is active anytime when at least one CAN module is in comm fail – regardless the protection is set
upon the lost of any specific CAN module.
Peripheral Module Comm Fail
6 back to Logical binary outputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 36
Description
This output can be used for control of any device, which has to be activated just before start. the output is
active for time period of Prestart Time (page 227). The output is deactivated 100 ms before the STARTER
(PAGE 501) output is activated.
Image 8.53 Engine start
Prestart