InteliLite4 AMF20 Global Guide
382
Nominal Power Split Phase 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 15772 Related applications AMF,MRS
Config level Standard
Setpoint visibility Conditioned by the setpoint Connection type 2 (page 379)
Description
Nominal power of the Gen-set for detected split-phase or mono phase connection. Generator Overload
BOC (page 260) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type 2 (page 379) is adjusted to Autodetect
and Autodetect detects connection type as Monophase or SplitphaseL1L2 or SplitphaseL1L3.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints
Subgroup:Configuration 3
Nominal RPM 3
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 100 .. 4 000 [RPM]
Default value 1 500 RPM Alternative config YES
Step 1 RPM
Comm object 15196 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Always
Description
Nominal engine speed (RPM - revolutions per minute).
Note: This value is used when binary input ALTERNATE CONFIG 3 (PAGE 439) is active.
6 back to List of setpoints