ECU Speed Adjustment 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 14338 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints
Nominal Power 2
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 12047 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the Gen-set. Generator Overload BOC (page 260) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type 2 (page 379) is adjusted to Monophase
or SplitphaseL1L2 or SplitphaseL1L3 or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect
detects connection type as 3Ph3Wire or High Leg D or 3Ph4Wire.
Note: This value is used when binary input ALTERNATE CONFIG 2 (PAGE 439) is active.
6 back to List of setpoints