InteliLite4 AMF20 Global Guide
260
Maintenance Timer 3 Protection
Setpoint group Maintenance Timers Related FW 1.3.0
Range [units] Warning / BOC [-]
Default value Warning Alternative config NO
Step [-]
Comm object 20588 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Type of the maintenance alarm of both Maintenance Timer 3 RunHours (page 259) and Maintenance
Timer 3 Interval (page 259).
6 back to List of setpoints
Group: Generator settings
Subgroup: Overload Protection
Overload BOC
Setpoint group Generator settings Related FW 1.3.0
Range [units] Overload Wrn (page 261) .. 200 [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 206)
Comm object 8280 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for overload of generator (in % of Nominal power) protection. Protection is BOC (Breaker
Open and Gen-set Cooldown).
Note: When there is no control of breakers, the type of protection is Sd not BOC.
6 back to List of setpoints