Overload Wrn
Setpoint group Generator settings Related FW 1.3.0
Range [units] 0 .. Overload BOC (page 260) [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 206)
Comm object 9685 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for overload of generator (in % of Nominal Power (page 206)) protection. This is only
warning.
6 back to List of setpoints
Overload Delay
Setpoint group Generator settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 5.0 s Alternative config NO
Step 0.1 s
Comm object 8281 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for protections Overload BOC (page 260) and Overload Wrn (page 261).
6 back to List of setpoints
Subgroup: Current Protection
Short Circuit BOC
Setpoint group Generator settings Related FW 1.3.0
Range [units] 100 .. 500 [%]
Default value 250 % Alternative config NO
Step 1 % of Nominal Current (page 207)
Comm object 8282 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Protection occurs when generator current reaches this preset threshold. Type of the protection is BOC.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
6 back to List of setpoints