InteliLite4 AMF20 Global Guide
261
Overload Wrn
Setpoint group Generator settings Related FW 1.3.0
Range [units] 0 .. Overload BOC (page 260) [%]
Default value 120 % Alternative config NO
Step 1 % of Nominal Power (page 206)
Comm object 9685 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold level for overload of generator (in % of Nominal Power (page 206)) protection. This is only
warning.
6 back to List of setpoints
Overload Delay
Setpoint group Generator settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 5.0 s Alternative config NO
Step 0.1 s
Comm object 8281 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for protections Overload BOC (page 260) and Overload Wrn (page 261).
6 back to List of setpoints
Subgroup: Current Protection
Short Circuit BOC
Setpoint group Generator settings Related FW 1.3.0
Range [units] 100 .. 500 [%]
Default value 250 % Alternative config NO
Step 1 % of Nominal Current (page 207)
Comm object 8282 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Protection occurs when generator current reaches this preset threshold. Type of the protection is BOC.
Note: When there is no control of breakers, the type of protection is Sd not BOC.
6 back to List of setpoints