InteliLite4 AMF20 Global Guide
206
Group: Basic settings
Subgroup: Name
Gen-Set Name
Setpoint group Basic settings Related FW 1.3.0
Range [units] 0 .. 15 characters [-]
Default value InteliLite Alternative config NO
Step [-]
Comm object 8637 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
User defined name, used for the controller identification at remote phone or mobile connection. Gen-set
Name is maximally 15 characters long and can be entered using InteliConfig or from controller's
configuration menu.
Note: If the Gen-set Name is "TurboRunHours", the running hours will be counted faster 1 minute in
real will represent 1 hour.
6 back to List of setpoints
Subgroup: Power settings
Nominal Power
Setpoint group Basic settings Related FW 1.3.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 8276 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the Gen-set. Generator Overload BOC (page 260) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type (page 209) is adjusted to Monophase or
Splitphase or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect detects connection type as
3Ph3Wire or High Leg D or 3Ph4Wire.
Note: To lock this setpoint against editing you also have to lock setpoint Nominal Power 1 (page
376), Nominal Power 2 (page 381) and Nominal Power 3 (page 386).
6 back to List of setpoints