ECU Speed Adjustment 1
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 0 .. 100 [%]
Default value 50 % Alternative config NO
Step 1 %
Comm object 14337 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if ECU is configured
Description
Enables to adjust engine speed in ECU via CAN bus. Nominal speed corresponds to 50%. This setpoint
should be used only for Volvo Penta and Scania engines. It has no effect on other engine brands.
Note: This value is used when any other alternate configuration is not active.
6 back to List of setpoints
Nominal Power 1
Setpoint group Alternate Config Related FW 1.3.0
Range [units] 1 .. 5 000 [kW]
Default value 200 kW Alternative config YES
Step 1 kW
Comm object 12046 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Nominal power of the Gen-set. Generator Overload BOC (page 260) protection is based on this setpoint.
Note: This setpoint is used when setpoint Connection type (page 209) is adjusted to Monophase or
SplitphaseL1L2 or SplitphaseL1L3 or 3Ph3Wire or High Leg D or 3Ph4Wire or when Autodetect
detects connection type as 3Ph3Wire or High Leg D or 3Ph4Wire.
Note: This value is used when any other alternate configuration is not active.
6 back to List of setpoints