InteliLite4 AMF20 Global Guide
439
LBI: A
Related FW 1.3.0 Related applications AMF,MRS
Comm object 859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
IMPORTANT: If LBO ECU POWER RELAY (PAGE 474) is used, change of alternate
configuration can be made only in prestart phase. So prestart has to be set up for enough
long time.
Alternate Config 2
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
IMPORTANT: If LBO ECU POWER RELAY (PAGE 474) is used, change of alternate
configuration can be made only in prestart phase. So prestart has to be set up for enough
long time.
Alternate Config 3
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 211
Description
This binary input can allow or block the AMF start. In case of running Gen-set in AUTO mode Gen-set
goes to cooling procedure and stops.
AMF Start Block
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 1008
Description
LBI is used to select AMF mode. It has higher priority than the setpoint Default Application Select (page
217).
Application AMF
6 back to Logical binary inputs alphabetically