InteliLite4 AMF20 Global Guide
245
Image 8.11 Staring speed overshoot › Ovespeed Sd
Image 8.12 Staring speed overshoot ‹ Ovespeed Sd
6 back to List of setpoints
Starting Overspeed Time
Setpoint group Engine protection Related FW 1.3.0
Range [units] 0 .. 255 [s]
Default value 5 s Alternative config NO
Step 1 s
Comm object 14108 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Time when Starting Overspeed Sd (page 244) level is used for overspeed protection. This time starts
countdown when starting RPM are reached.
6 back to List of setpoints
Starting Overspeed Protection
Setpoint group Engine settings Related FW 1.3.0
Range [units] OverSpd Sd / NextStartAt [-]
Default value OverSpd Sd Alternative config NO
Step [-]
Comm object 15808 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
The setpoint allows user to chose which kind of protection will be triggered if speed limit is reached during
Starting Overspeed Time (page 245).