InteliLite4 AMF20 Global Guide
551
Alarm Type MP
Alarmlist message Mains Overfrequency
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm is active when Mains frequency is above the setpoint Mains
Overfrequency (page 277) for the period longer than Mains < > Frequency
Delay (page 281).
Mains Overfrequency
6 back to List of alarms level 1
Alarm Type MP
Alarmlist message Mains Underfrequency
Alarm evaluated All the time
Related applications AMF,MRS
Description
This alarm is active when Mains frequency is bellow the setpoint Mains
Underfrequency (page 279) for the period longer than Mains < > Frequency
Delay (page 281).
Mains Underfrequency
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Wrn Mains Voltage Detected
Alarm evaluated Gen-set is running
Related applications AMF,MRS
Description
This alarm occurs when setpoint Default Application Select (page 217) is
adjusted to MRS and voltage is detected on mains.
Wrn Mains Voltage Detected
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Oil Pressure
Alarm evaluated Gen-set is running
Related applications AMF,MRS
Description
This alarm indicates that the oil pressure is lower than the pressure set in the
setpoint.
Wrn Oil Pressure
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Wrn Wrong GCB Control Mode
Alarm evaluated all the time
Related applications AMF,MRS
Wrn Wrong GCB Control Mode