277
Mains Voltage Unbalance Delay
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 2.0 s Alternative config NO
Step 0.1 s
Comm object 8447 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Delay for Mains Voltage Unbalance (page 276) protection.
6 back to List of setpoints
Subgroup: Mains Frequency Limits
Mains Overfrequency
Setpoint group Mains Settings Related FW 1.3.0
Range [units] Mains Underfrequency (page 279) .. 150 [%]
Default value 102.0 % Alternative config NO
Step 1.0 % of Nominal Frequency (page 215)
Comm object 8310 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Threshold for Mains overfrequency.
6 back to List of setpoints