InteliLite4 AMF20 Global Guide
276
Mains Overvoltage Delay
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 2.0 s Alternative config YES
Step 0.1 s
Comm object 8306 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Delay for Mains Overvoltage (page 272) protection.
6 back to List of setpoints
Mains Undervoltage Delay
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 0.0 .. 600.0 [s]
Default value 2.0 s Alternative config YES
Step 0.1 s
Comm object 8308 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Delay for Mains Undervoltage (page 274) protection.
6 back to List of setpoints
Mains Voltage Unbalance
Setpoint group Mains Settings Related FW 1.3.0
Range [units]
1 .. 150 [%] of Nominal Voltage Ph-Ph (page 211) or Nominal Voltage Ph-N
(page 211)
Default value 10 % Alternative config NO
Step 1 %
Comm object 8446 Related applications AMF
Config level Advanced
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Threshold for Mains voltage unbalance.
6 back to List of setpoints

Table of Contents