InteliLite4 AMF20 Global Guide
272
Subgroup: Mains Voltage Limits
Mains Overvoltage
Setpoint group Mains Settings Related FW 1.3.0
Range [units] Mains Undervoltage (page 274) .. 150 [%]
Default value 110 % Alternative config NO
Step 1 % of Nominal Voltage Ph-Ph (page 211)
Comm object 8305 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Threshold for Mains overvoltage. All three phases are checked. Maximum out of three is used.
6 back to List of setpoints