EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #271 background imageLoading...
Page #271 background image
InteliLite4 AMF20 Global Guide
271
Image 8.17 Transfer Delay 1
If some delay between MCB FEEDBACK (PAGE 453) deactivation and closing of GCB CLOSE/OPEN (PAGE
480) output is required, then the Transfer Delay must be set to sum of "MCB opening" + "Delay" time.
Delay used in dual operation function. This delay is used when load from first Gen-set is transferred to
second Gen-set. Delay starts to countdown when GCB of first Gen-set is open. When this delay
countdown, GCB of second Gen-set is closed. This delay is important for correct function of external
interlock.
Image 8.18 Transfer Delay 2
6 back to List of setpoints