InteliLite4 AMF20 Global Guide
274
Mains Undervoltage
Setpoint group Mains Settings Related FW 1.3.0
Range [units] 50 .. Mains Overvoltage (page 272) [%]
Default value 60 % Alternative config YES
Step 1 % of Nominal Voltage Ph-Ph (page 211)
Comm object 8307 Related applications AMF
Config level Standard
Setpoint visibility Conditioned by the setpoint Default Application Select (page 217)
Description
Threshold for Mains undervoltage. All three phases are checked. Minimum voltage out of three phases is
used.
6 back to List of setpoints