InteliLite4 AMF20 Global Guide
247
Oil Pressure Sd
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 10.0 [bar]
Default value 1.0 bar Alternative config NO
Step 0.1 bar
Comm object 65533 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for Sd Oil Pressure (page 565) user protection.
6 back to List of setpoints
Coolant Temp Delay
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 3600.0 [s]
Default value 5.0 s Alternative config NO
Step 0.1 s
Comm object 65532 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Wrn Coolant Temp (page 536)/BOC Coolant Temp (page 565) user protection.
6 back to List of setpoints
Coolant Temp Wrn
Setpoint group User Setpoints Related FW 1.3.0
Range [units] -16 .. 120 [°C]
Default value 80 °C Alternative config NO
Step 1 °C
Comm object 65531 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for Wrn Coolant Temp (page 536) user protection.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals