248
Coolant Temp BOC
Setpoint group User Setpoints Related FW 1.3.0
Range [units] -16 .. 120 [°C]
Default value 90 °C Alternative config NO
Step 1 °C
Comm object 65530 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for BOC Coolant Temp (page 565) user protection.
6 back to List of setpoints
Coolant Temp Low Delay
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 3600.0 [s]
Default value 0.0 s Alternative config NO
Step 0.1 s
Comm object 65529 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Wrn Coolant Temp Low (page 536) user protection.
6 back to List of setpoints
Coolant Temp Low Wrn
Setpoint group User Setpoints Related FW 1.3.0
Range [units] -16 .. 120 [°C]
Default value 5 °C Alternative config NO
Step 1 °C
Comm object 65528 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for Wrn Coolant Temp Low (page 536) user protection.
6 back to List of setpoints