EasyManuals Logo

ComAp InteliLite 4 AMF 20 User Manual

ComAp InteliLite 4 AMF 20
620 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #249 background imageLoading...
Page #249 background image
InteliLite4 AMF20 Global Guide
249
Fuel Level Delay
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0.0 .. 3600.0 [s]
Default value 10.0 s Alternative config NO
Step 0.1 s
Comm object 65527 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Delay for Wrn Fuel Level (page 536)/BOC Coolant Temp (page 565) user protection.
6 back to List of setpoints
Fuel Level Wrn
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0 .. 100 [%]
Default value 20 % Alternative config NO
Step 1 %
Comm object 65526 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for Wrn Fuel Level (page 536) user protection.
6 back to List of setpoints
Fuel Level BOC
Setpoint group User Setpoints Related FW 1.3.0
Range [units] 0 .. 100 [%]
Default value 10 % Alternative config NO
Step 1 %
Comm object 65525 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Threshold for BOC Coolant Temp (page 565) user protection.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals