InteliLite4 AMF20 Global Guide
250
Subgroup:Fuel Pump
Fuel Pump On
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0 .. Fuel Pump Off (page 251) [%]
Default value 20 % Alternative config YES
Step 1 %
Comm object 10100 Related applications AMF,MRS
Config level Advanced
Setpoint visibility All the time
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 477) on.
Image 8.13 Fuel Pump On
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 449) is configured then binary
output FUEL PUMP (PAGE 477) is control by this binary input. Setpoints Fuel Pump On and
Fuel Pump Off (page 251) are not evaluated!
Note: Value from analog input has higher priority than ECU.