InteliLite4 AMF20 Global Guide
251
Fuel Pump Off
Setpoint group Engine settings Related FW 1.3.0
Range [units] Fuel Pump On (page 250) .. 100 [%]
Default value 90 % Alternative config YES
Step 1 %
Comm object 10101 Related applications AMF,MRS
Config level Advanced
Setpoint visibility All the time
Description
Threshold level for switching the binary output FUEL PUMP (PAGE 477) off.
Image 8.14 Fuel Pump Off
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 449) is configured then binary
output FUEL PUMP (PAGE 477) is control by this binary input. Setpoints Fuel Pump On (page
250) and Fuel Pump Off are not evaluated!
Note: Value from analog input has higher priority than ECU.
6 back to List of setpoints