InteliLite4 AMF20 Global Guide
252
Transfer Wrn Delay
Setpoint group Engine settings Related FW 1.3.0
Range [units] Disabled / 1 .. 600 [s]
Default value 30 s Alternative config YES
Step 1 s
Comm object 10685 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Visible only if the logical binary output FUEL PUMP (PAGE 477) is configured
Description
If the controller does not see the fuel increase during fuel transfer within this time alarm AL Fuel Transfer
Failed (page 536) will be displayed and the FUEL PUMP (PAGE 477) will be turned off. Alarm AL Fuel
Transfer Failed (page 536) will be displayed but this alarm becomes immediately inactive and it will be
possible to delete this message by the Fault reset button. If the fault is deleted the controller will initiate the
transfer again.
6 back to List of setpoints
Subgroup: Battery Protections
Battery Undervoltage
Setpoint group Engine settings Related FW 1.3.0
Range [units] 8.0 V .. Battery Overvoltage (page 253) [V]
Default value 18.0 V Alternative config NO
Step 0.1 V
Comm object 8387 Related applications AMF,MRS
Config level Standard
Setpoint visibility Always
Description
Warning threshold for low battery voltage.
6 back to List of setpoints