InteliLite4 AMF20 Global Guide
449
Related FW 1.3.0 Related applications AMF,MRS
Comm object 694
Description
This binary input is used for manual control of binary output FUEL PUMP (PAGE 477). The output is
deactivated automatically as soon as fuel level reaches 100%.
Note: This binary input is basically designed for ON and OFF switch (switch with arrestment in these
positions) because controller reacts to rising and falling edge of signal in this input.
IMPORTANT: When binary input FUEL PUMP ON/OFF (PAGE 449) is configured then binary
output FUEL PUMP (PAGE 477) is control by this binary input.
IMPORTANT: It is necessary to configure analog input FUEL LEVEL (PAGE 508) for proper
function of this binary input.
Fuel Pump On/Off
6 back to Logical binary inputs alphabetically
LBI: G
Related FW 1.3.0 Related applications AMF,MRS
Comm object 193
Description
Binary input has the same function as the GCB button on the InteliLite 4 front panel. It is evaluated in
MAN mode only.
GCB Button
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 62
Description
When this LBI is active, it is not possible to close GCB – LBO GCB Close/Open, GCB ON Coil cannot be
activated by panel GCB close button, or close command or by auto command.
GCB Disable
6 back to Logical binary inputs alphabetically

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite 4 AMF 20 and is the answer not in the manual?

ComAp InteliLite 4 AMF 20 Specifications

General IconGeneral
BrandComAp
ModelInteliLite 4 AMF 20
CategoryController
LanguageEnglish

Related product manuals