InteliLite4 AMF20 Global Guide
448
Related FW 1.3.0 Related applications AMF,MRS
Comm object 45
Description
This input is designed to allow the Gen-set system or breakers to be controlled externally, not by the
controller. This feature can be useful in case of some failure, which disables the Gen-set or breakers to be
controlled by the controller, but the gen-set itself is operational.
The controller behaves in the following way:
Shows the text EmergMan in the engine status on the main screen.
Stops all functions regarding the Gen-set or breaker control, deactivates all outputs related to it.
Stop Fail alarm is not being evaluated and stop solenoid is not activated if nonzero speed is
detected.
When the input is deactivated, the controller takes control according to the situation in the moment
of deactivation, i.e. the Gen-set remains running loaded if it was running and GCB was closed in the
moment the input was deactivated.
Emergency MAN
6 back to Logical binary inputs alphabetically
Related FW 1.3.0 Related applications AMF,MRS
Comm object 40
Description
The shutdown procedure will start immediately when this input is activated.
Note: In case of controller hardware or software fail, safe stop of the engine doesn’t have to be
ensured. To back-up the Emergency Stop function it is recommended to connect separate circuit for
disconnection of Fuel Solenoid and Starter signals.
For more detail see chapter Recommended wiring.
Emergency Stop
6 back to Logical binary inputs alphabetically
LBI: F
Related FW 1.3.0 Related applications AMF,MRS
Comm object 191
Description
Binary input has the same function as Fault Reset button on the InteliLite 4 front panel.
Fault Reset Button
6 back to Logical binary inputs alphabetically