InteliLite4 AMF20 Global Guide
243
D+ Threshold
Setpoint group Engine settings Related FW 1.3.0
Range [units] 0..100 [%]
Default value 80 % Alternative config NO
Step 1 %
Comm object 14959 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 241) is not set to Disabled value.
Description
This setpoint adjusts threshold level for D+ Function (page 241).
6 back to List of setpoints
D+ Delay
Setpoint group Engine settings Related FW 1.3.0
Range [units] 1..255 [s]
Default value 1 s Alternative config NO
Step 1 s
Comm object 14960 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 241) is not set to Disabled value.
Description
This setpoint adjusts delay for D+ Function (page 241). This delay is used for:
Alarm Wrn Charging Alternator Fail (page 537).
For engine running condition disengagement of starter
6 back to List of setpoints
D+ Alarm Type
Setpoint group Engine settings Related FW 1.3.0
Range [units] No Protec/Wrn/Sd [-]
Default value Wrn Alternative config NO
Step [-]
Comm object 15751 Related applications AMF,MRS
Config level Advanced
Setpoint visibility Only if setpoint D+ Function (page 241) is not set to Disabled value.
Description
This setpoint adjusts type of alarm Wrn Charging Alternator Fail (page 537).
6 back to List of setpoints