Alarm Type SD
Alarmlist message Sd Charging Alternator Fail
Alarm evaluated Engine running only
Related applications AMF,MRS
Description
This alarm is issued if the engine is running and the voltage on the D+ terminal is
lower than D+ Threshold (page 243) of the controller supply voltage. This alarm
works similar to the red "battery" alarm indicator on a vehicle dashboard. The
setpoint has to be in Charge Fail or Enabled position to enable this alarm.
Wrn Charging Alternator Fail
6 back to List of alarms level 2
Alarm Type WRN
Alarmlist message Wrn Stop Fail
Alarm evaluated While the engine shall be stopped
Related
applications
AMF,MRS
Description
This alarm occurs if the Gen-set shall be stopped, but some symptom indicates that
it is not stopped. The period when the Gen-set shall be stopped begins after the
FUEL SOLENOID (PAGE 477) has been switched off and time delay Stop Time (page
240) has elapsed and lasts for the entire time the FUEL SOLENOID (PAGE 477) or
STARTER (PAGE 501) are off.
Image 8.72 Stop Fail
Note: Gen-set cannot be started until this alarm is inactive and reset.
Wrn Stop Fail
6 back to List of alarms level 1
Alarm Type WRN
Alarmlist message Wrn Maintenance Timer 1 RunHours
Alarm evaluated All the time
Related applications AMF,MRS
Description
The alarm is active when the value Maintenance Timer 1 RunHours (page
412) reaches 0.
The value is adjustable by setpoint Maintenance Timer 1 RunHours (page
Wrn Maintenance Timer 1 RunHours