InteliLite4 AMF20 Global Guide
192
Reading Nominal power
Export table of values from InteliConfig
Table: Values
Allowed MODBUS functions: 03, 04
Register
address
Com.Obj. Name Dimension Type Len Dec Min Max Group
01227 9018
Nominal
Power
kW Integer 2 0 0 32767 Generator
Request: (Numbers in Hex)
01 03 04 CC 00 01 45 05
Controller address Modbus function
Register address
04CC
hex
=
1228
dec
Number of registers CRC
Response: (Numbers in Hex)
01 03 02 00 C8 B9 D2
Controller address Modbus function
Length of data
02
hex
= 2 bytes
read
Data
00C8
hex
=
200
dec
CRC
Read nominal power is 200kW.