InteliLite4 AMF20 Global Guide
414
Maintenance Timer 3 Interval
Value group Statistics Related FW 1.3.0
Units days
Comm object 16389 Related applications AMF,MRS
Description
Countdown until next maintenance 3.
Statistic value for Maintenance Timer 3 Interval (page 259).
6 back to List of values
Num E-Stops
Value group Statistics Related FW 1.3.0
Units [-]
Comm object 11195 Related applications AMF,MRS
Description
Emergency stop alarms counter.
Note: This value counts only in case that Gen-set was stopped due to E-Stop or Emergency Stop.
6 back to List of values
Shutdowns
Value group Statistics Related FW 1.3.0
Units [-]
Comm object 11196 Related applications AMF,MRS
Description
Shutdown alarms counter. This counter counts all occurrences of a shutdown alarm, not only real
shutdowns of the Gen-set, i.e. the counter is increased by 2 if two shutdown alarms appear
simultaneously.
6 back to List of values
Total Fuel Consumption
Value group Statistics Related FW 1.3.0
Units L
Comm object 9040 Related applications AMF,MRS
Description
Value containing total amount of consumed fuel by engine. The controller automatically updates this value
every 30s. The controller can calculate it in three ways:
Direct reading from ECU
Calculation based on actual fuel consumption reading from ECU
Calculation from fuel level drop in tank (using Fuel Level Analog Input)
6 back to List of values