InteliLite Global Guide
134
Still engine conditions
Engine speed (RPM) < Starting RPM (page 207) or
Oil pressure < Starting Oil Pressure (page 208) or
Binary input OIL PRESSURE (PAGE 561) is in logical 1 or
Generator voltage < 50 V (any phase)
Note: When the engine was running before and all above conditions are fulfilled, additional 2 s delay is
necessary to confirm “still engine”.
When any engine running conditions are appeared on still engine than the Wrn Stop Fail (page 701) is
activated with following delay:
for generator voltage from 10 V to < 50 % of nominal voltage, Wrn Stop Fail has delay 1 s
for generator voltage > 50 % of nominal voltage, Wrn Stop Fail has delay 200 ms
Oil pressure > Starting Oil Pressure (page 208), Wrn Stop Fail has delay 1 s
Binary input OIL PRESSURE (PAGE 561) is in logical 0, Wrn Stop Fail has delay 1 s
for detected RPM, there is no delay.
Stop engine conditions
If no engine running conditions are validated than the controller will wait extra 12 s before leaving the Machine
state Stop and than it will release the STOP SOLENOID (PAGE 634) output.
Image 5.30 Engine stops in Stop Time (page 219)
When the total time of stopping will exceed setpoint Stop Time (page 219) than the Wrn Stop Fail (page 701)
and binary outputs are activated. The controller will continuously try to stop the engine.