When the Rental Timer 2 (page 319) elapsed during engine run the gen-set will not stop immediately. The
adjustable Rental Timer BOC (page 321) timer will start in this moment. The engine will be cooled and
stopped when the Rental Timer BOC (page 321) time elapsed.
Image 8.62 Rental Timer 2
The Running Hours Overrun counter will start increment when the engine is continue running after the Rental
Timer 2 (page 319) elapsed.
Note: There is no priority between Rental Timer 1 and Rental Timer 2. The sooner timer will activated the
Rental Timer BOC (page 321) protection.
6 back to List of setpoints

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65