InteliLite Global Guide
499
LBI: A
Related FW 1.9.0 Related applications AMF, MRS
Comm object 1
Description
When this input is closed, no setpoints can be adjusted from controller’s front panel and controller mode
(OFF / MAN / AUTO / TEST) cannot be changed.
Note: Access Lock does not protect setpoints and mode changing from InteliConfig. To avoid
unqualified changes the selected setpoints have to be password protected.
Also the buttons Fault Reset and Horn Reset are not blocked at all and buttons Start and Stop
in MAN mode are not blocked.
Access Lock
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 859
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the second set (setpoints with number 2).
IMPORTANT: If LBO ECU POWER RELAY (PAGE 570) is used, change of alternate configuration
can be made only in prestart phase. So prestart has to be set up for enough long time.
Alternate Config 2
6 back to Logical binary inputs alphabetically
Related FW 1.9.0 Related applications AMF, MRS
Comm object 860
Description
This binary input can switch between configuration sets. When this binary input is active, setpoints in
Alternate Config group are switched to the third set (setpoints with number 3).
IMPORTANT: If LBO ECU POWER RELAY (PAGE 570) is used, change of alternate configuration
can be made only in prestart phase. So prestart has to be set up for enough long time.
Alternate Config 3
6 back to Logical binary inputs alphabetically