Description
Binary input also can be adjusted like alarm. In this case message in alarmlist
contains prefix - Sd and binary input name. This alarm occurs, when appropriate
binary input is active.
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Coolant Temp
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the coolant temperature is higher than the temperature set
in Coolant Temperature Sd (page 210) setpoint.
Sd Coolant Temp
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Current Unbalance
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm evaluates the unbalance of the phase currents, i.e. the difference
between highest and lowest phase current at any given time. The following
setpoints are related to it:
Current Unbalance BOC (page 230) adjusts the maximum allowed
difference between the highest and lowest phase current at any given time.
Current Unbalance BOC Delay (page 230) adjusts the alarm delay.
Sd Current Unbalance
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Earth Fault Current
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm indicates that the value of earth fault current is higher than adjusted
limit. The following setpoints are related to it:
Earth Fault Sd (page 387) adjusts the maximum allowed earth fault
current.
Earth Fault Delay (page 386) adjusts the alarm delay.
Sd Earth Fault Current
6 back to List of alarms level 2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals