InteliLite Global Guide
681
Related applications AMF, MRS
Description
This alarm indicates that the oil pressure is lover than the pressure set in Oil
Pressure Sd (page 208) setpoint.
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overload
Alarm evaluated All the time
Related applications AMF, MRS
Description
The alarm is issued when the gen-set power is over the limit for time period longer
than the delay. The behavior of the overload alarm is adjusted by the following
setpoints:
Overload BOC (page 227) adjusts the overload limit.
Overload Delay (page 227) adjusts the delay
Sd Overload
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd Overspeed
Alarm evaluated All the time
Related applications AMF, MRS
Description
This alarm occurs immediately when the engine speed has exceeded the limit. The
behavior of the overspeed alarm is adjusted by the following setpoints:
Overspeed Sd (page 207) adjust the overspeed limit
Overspeed Overshot (page 207) adjust the additional overspeed limit
Overspeed Overshot Period (page 208) adjust the time period of
additional overspeed limit
Sd Overspeed
6 back to List of alarms level 2
Alarm Type Shutdown
Alarmlist message Sd RPM Measurement Fail
Alarm evaluated During cranking
Related applications AMF, MRS
Description
The alarm is issued if the engine speed has not exceeded the Starting RPM (page
191) within the Maximum Cranking Time (page 190), although some of
additional running engine indication sources indicate that the engine has started.
Sd RPM Measurement Fail
6 back to List of alarms level 2

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp InteliLite AMF25 and is the answer not in the manual?

ComAp InteliLite AMF25 Specifications

General IconGeneral
Inputs8 binary inputs
Outputs8 binary outputs
Power Supply8-36 V DC
CommunicationRS232, RS485
Operating Temperature-20°C to +70°C
Supported GeneratorsDiesel, gas
Controller TypeAutomatic Mains Failure Controller
ProtectionIP65

Related product manuals