InteliLite Global Guide
698
Alarm Type Warning
Alarmlist message Wrn Generator > Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Overfrequency Wrn (page 248)
Generator <> Frequency Delay (page 249)
Wrn Generator > Frequency
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Generator < Frequency
Alarm evaluated Generator excited only
Related applications AMF, MRS
Description
This alarm evaluates the generator frequency in the phase L1. The following
setpoints are related to it:
Generator Underfrequency Wrn (page 249)
Generator <> Frequency Delay (page 249)
Wrn Generator < Frequency
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Check DPF Status
Alarm evaluated When ECU is configured
Related applications AMF, MRS
Description
This alarm occurs when ECU send alarm message about Tier IV protection.
Note: Tier IV protection have to be supported by ECU.
Wrn Check DPF Status
6 back to List of alarms level 1
Alarm Type Warning
Alarmlist message Wrn Mains Voltage Detected
Alarm evaluated Gen-set is running
Related applications AMF
Description
This alarm occurs when setpoint Operation Mode (page 199) is adjusted to MRS
and voltage is detected on mains.
Wrn Mains Voltage Detected
6 back to List of alarms level 1