InteliLite Global Guide
730
Technical data
Dimension (W × H × D) 110 × 110 × 46 mm (4.3” × 4.3” × 1.8”)
Weight 237.5 grams
Interface to controller CAN1
Analog inputs (not electric separated) 8, no galvanic separated
Measuring ±100 mV
Accuracy ± 0.1 % of actual value + ± 100 µV (± 3 °C)
Internal sensor for measuring cold junction - Accuracy ±1 °C in temperature range -20 °C ÷ +70 °C
Galvanic separation
CANbus is galvanic separated from the
measurement and power supply.
All analog inputs are galvanic separated from
power supply.
Analog inputs are not galvanic separated
between channels
Power supply 8 to 36 V DC
Protection IP20
Current consumption 35 mA at 24 V ÷ 100 mA at 8 V
Storage temperature - 40 °C to + 80 °C
Operating temperature - 30 °C to + 70 °C
Heat radiation 2 W
Thermocouples galvanically separated and galvanically non-separated are supported.
Inteli AIO9/1
Inteli AIO9/1 module is extension module equipped with analog inputs and outputs – designed for DC
measurement.
The detection of communication speed is indicated by fast flashing of status LED. Once the speed is detected
the module remains set for the speed even when the communication is lost. Renewal of communication speed
detection is done by reset of the module.