EasyManuals Logo

ComAp IS-NTC-BB Installation Guide

ComAp IS-NTC-BB
149 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
IGS-NT Installation Guide
143
Mechanical dimensions: 96 x 27 x 43 mm , DIN rail (35 mm) mounted
20.11.1. IG-AVRi Trans/LV
Primary voltage 1: 230-277 VAC
Absolute low limit: 230 VAC 20%
Absolute high limit: 277 VAC + 20%
Primary voltage 2: 400-480 VAC
Absolute low limit: 400 VAC 20%
Absolute high limit: 480 VAC + 20%
Frequency: 50 60 - 400 Hz
Secondary voltage: 18 V AC, 5 VA
Operating temperature -30..+70
o
C
20.11.2. IG-AVRi Trans/100
Primary voltage: 100 120 VAC
Absolute low limit: 100 VAC 20%
Absolute high limit: 120 VAC + 20%
Frequency: 50 - 60 400Hz
Secondary voltage: 18 V AC
Operating temperature -30..+70
o
C
20.12. IGS-PTM
Voltage supply 8-36V DC
Consumption 0,1A depend on supply voltage
Mechanical dimensions: 40 x 9 x 45 mm , DIN rail (35 mm) mounted
Interface to controller CAN
Operating temperature -30..+70
o
C
20.12.1. Binary inputs
Number of inputs 8
Input resistance 4,7 k
Input range 0 - 36 VDC
Switching voltage level for close contact indication 0 - 2 V
Max voltage level for open contact indication 8-36 V
20.12.2. Binary open collector outputs
Number of outputs 8
Maximum current 0,5 A
Maximum switching voltage 36 VDC

Table of Contents

Other manuals for ComAp IS-NTC-BB

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ComAp IS-NTC-BB and is the answer not in the manual?

ComAp IS-NTC-BB Specifications

General IconGeneral
BrandComAp
ModelIS-NTC-BB
CategoryController
LanguageEnglish

Related product manuals